Glycol levels: is your chilled water system at risk this winter?

As the UK starts to experience sub-zero temperatures, so the troubles can start for those responsible for managing or maintaining HVAC and chilled water (CHW) systems. During winter months, system pipework is exposed to ambient temperatures low enough to freeze cooling water.

If the water is inadequately protected and starts to freeze, blockages and leaks often occur, efficiencies are drastically reduced, and there is a significant risk of pipes bursting - potentially causing thousands of pounds worth of damage, unplanned maintenance and costly downtime.

Systems that have not been properly maintained are particularly at risk, or those that have been altered or upgraded (as it may be difficult to evaluate the quality and protection qualities of the water). Cooling systems are often topped up with uninhibited water, subsequently leading to a dilution of the antifreeze and inhibitors.

Incorrect glycol levels at this time of year can impact hugely on any cooling system, potential issues include:

System failure and repairs

If freezing water is left to expand past the diameter of condenser pipes, the internal pressure will cause them to rupture. As well as the potential repair costs, many firms are forced to close down for days or even weeks.

Flood damage

Not only can a water leak cause damage to property, stock and assets, but the interruption to the day-to-day business operations can have devastating financial consequences.

Your equipment warranty may be voided

Many chiller manufacturers will discredit their warranties if you have not maintained the correct levels of glycol in chilled systems - resulting in the warranty for your equipment being voided.

Increased energy costs, reduced output

Pumps will have to work harder to push water through the pipes, as the water starts to freeze in the system. The decrease in flow velocity will reduce production and increase operational costs.

Types of Glycol

The two major types of glycol used in chilled water and closed loop systems are Ethylene Glycol and Propylene Glycol. Ethylene glycol offers the most efficient heat transfer, is significantly less viscous than PG and unit cost is usually lower. The main drawback however is its toxicity to humans and animals.

Propylene glycol was developed to replace Ethylene Glycol for use in food and beverage processing systems or where there is a requirement for a non-toxic classification. PG has a much lower capacity for efficient heat transfer, compared with Ethylene Glycol based mixtures - It is also much more viscous at low temperatures and thus provides more of a challenge to pump.

In 2010 Hydratech added Coolflow DTX to their range of process cooling fluids. DTX is a high-performance non-toxic heat transfer fluid that is based on ethylene glycol, blended with a detoxification additive. The game changing fluid combines the thermal efficiency and low viscosity associated to ethylene glycol, with the non-toxic rating of propylene glycol. The list of DTX adopters is now extensive and includes Arla Foods, Mϋller Dairy, Waitrose, Airbus, Siemens and BrewDog.

How much glycol will I need for my system?

Selecting the correct type and concentration of glycol is very important. The glycol type should already be known and recorded in the commissioning documents or maintenance logs for your systems.

Hydratech Services can assist with glycol determination analysis if it is not known – it is especially important to verify this for food or beverage process applications.

Too much glycol or too high a % will cause system inefficiencies through reduced heat transfer ability and pumping capacity. Not enough glycol, or too low a % can lead to expensive freeze-ups and potential biological fouling issues.

Typically, external systems susceptible to freezing over winter months will need anti-freeze protection down to the lowest expected ambient temperature - with a margin of +10% advised for safety. (Note: Lowest temps ever recorded in UK -26.1°C - January 1982).

As a guide (taking an average between EG & PG, and considering the differing levels of freeze protection per percentage) an installed concentration of 40% v/v (glycol by volume in water) will give you frost protection down to -25°C.

High glycol concentrations can impact system efficiency and a trade off exists between anti-freeze protection and year-round performance and COP. Some therefore choose to run with glycol/antifreeze over winter months and plain water when the risk of ambient freezing is no longer an issue.

For year-round protection against internal corrosion, scaling and biological fouling, it is recommended that the glycol is fully inhibited and monitored every 6 months. Hydratech recommend a minimum concentration of 25% v/v for their inhibited glycols – this would provide a freeze protection average of -10°C.

Glycol price soar: why it’s time to consider Coolflow DTX

Extreme weather, global pandemic and logistical chaos has rocked the world’s chemical markets, sending prices soaring. For many well-known companies, this instability has acted as a catalyst to make the switch to Coolflow DTX.

The cost saving benefits of dosing a new or existing (retrofit) system with DTX are particularly favourable in the current economic climate. For example, given the current rates, a potential saving of around 80% per installation could be made if DTX replaced PG in a proposed 20,000 Litre system (protected to -15°C).

From concept and design, to tender and retrofit, DTX has proved (for the last 10 years) to be a highly effective alternative to propylene glycol. At nearly half the cost of PG per installation, surely it's time to make the switch to DTX.

For more information on glycol concentrations, our antifreeze range, or fluid testing to verify condition and frost protection - email: info@hydratech.co.uk or call 01792 586800