| Anti-Freeze |
Optimum Flow |
Non Toxic |
Biodegradeable |
Corrosion Control |
Quality Assured |
|
High
Efficiency Non-Toxic Secondary Refrigerant Antifreeze, based on Ethylene
Glycol blended with patented DeTox™ additive and BS6580 proven Corrosion,
Scale and Biological Inhibitors. |
Density: |
1.04
– 1.15 g/cm3 depending on inhibitors |
PH: |
7.5
– 10.5 depending on inhibitors. |
Boiling
point: |
>100°C |
COOLFLOW DTX has been especially
formulated to exploit the advantages Ethylene Glycol has over Propylene Glycol.
Specifically;
- More efficient heat transfer.
- Easier to
pump, especially at low temperatures.
- Less volume for the same freeze protection.
- Cheaper per litre.
Although based on Ethylene
Glycol, COOLFLOW DTX has been tested and classified as Non-Toxic1 by an EPA2 certified laboratory. Previously Propylene Glycol was the only non-toxic glycol
available. That is no longer the case.3
Hydratech in alliance with Evans Cooling
Systems, Inc. have developed and patented the DeTox™ additive. DeTox™ prevents
Ethylene Glycol from being metabolised (during digestion) into toxic by-products,
which cause kidney failure, blindness and death.4 Tests carried out on COOLFLOW
DTX confirmed the toxicity was “so low that it was impossible to determine
an LD505 value”.
The DeTox™ additive has very little effect
on heat transfer or antifreeze performance. In fact similar volumes of COOLFLOW
DTX or Ethylene Glycol are required to achieve a specific freeze protection.
COOLFLOW DTX mixtures are readily biodegradable
(90% over ten days) and will not remain in the environment or bio-accumulate.
COOLFLOW DTX contains synergistic corrosion
inhibitors to protect metals commonly found in such systems. It has been tested
in accordance with BS5117 and found to meet BS6580 corrosion standards for
mild & stainless steel, aluminium,
copper, brass and cast iron. Zinc or galvanised components are not recommended
for use with closed loop cooling or heating systems.
COOLFLOW DTX also contains
scale and biological inhibitors to help prevent fouling – thus promoting long
operational life and high thermal efficiency.
COOLFLOW DTX is miscible with water in all proportions and can protect RAC systems down
to -50°C depending on concentration.
COOLFLOW DTX is a clear, slightly viscous
liquid. It is mildly sweet to the taste and has a non-pungent but characteristic
aroma.
COOLFLOW DTX exhibits super-cooling characteristics
and mixtures containing in excess of 50% by volume do not freeze solid, alleviating
any concern over possible expansion and burst damage.

As per BSRIA guide AG 1/2001.1 all pipe-work
systems should be clean and free from biological contamination prior to commissioning.
To minimise corrosion air 6 ingress
should be minimized. A pressurised system is best.
Determine the total system volume
and add COOLFLOW DTX to the system according to the minimum
operating temperature required (see table). The minimum dose of COOLFLOW
DTX should not be less than
22% of the system volume and the maximum does not normally exceed 60%. We recommend
the use of deionised, distilled or UltraPure™ water for this dilution. Avoid
water containing high levels of calcium salts or Chlorides [Cl-].
Health & Safety: Please refer to the associated
Safety Data Sheet.
Shelf Life: 3 years when stored in sealed containers
out of direct sunlight.
Available in: 5, 10, 15, 20, 25, 205 & 1,000 litre
containers and in bulk tankers.
COOLFLOW DTX can also be supplied pre-mixed,
as a Ready-To-Use solution.

|
% v/v of COOLFLOW DTX in the system
|
|
|
|
1.356 |
-15 |
28% |
1.362 |
-20 |
33% |
1.367 |
-25 |
38% |
1.372 |
-30 |
42% |
1.376 |
-35 |
46% |
1.380 |
When measuring
the percentage of COOLFLOW DTX in the system use a refractometer.

SUREFLOW Support Services ensure that end
users and distributors receive the full benefit of working with a specialist
manufacturer. E.g.;

1 According to the Hodge & Sterner Toxicity
Scale, an LD50 rating between 500 – 5,000 mg/kg body-weight (bw) is classed
as “Slightly Toxic” and anything above 15,000 mg/kg bw is classed as “Relatively
Harmless” I.E. Non-Toxic.
2 EPA = United States Environmental Protection
Agency.
3 COOLFLOW DTX LD50 (Oral Rat) >21,000 mg/kg bw.
Propylene Glycol LD50 20,000
mg/kg bw.
Ethylene Glycol LD50 4,700 mg/kg bw.
4 According to the US Department
of Health & Human Services as little as 150ml of Ethylene Glycol can lead
to death and much smaller amounts can lead to renal failure in humans.
5 LD50
= Lethal Dose (oral) that causes the death of 50% of the lab rats.
6 Oxygen
feeds the corrosion process and consumes inhibitors.
|
Ecologically
and Environmentally Friendly Non-Toxic Secondary Refrigerant Antifreeze.
Based on Refined Vegetable Extracts blended with BS6580 proven Corrosion,
Scale and Biological Inhibitors. |
|
Non-Toxic
Secondary Refrigerant Antifreeze. Based on Propylene Glycol, blended
with BS6580 proven Corrosion, Scale and Biological inhibitors. |
|
Industrial
Grade Secondary Refrigerant Antifreeze. Based on Ethylene Glycol, blended
with BS6580 proven Corrosion, Scale and Biological Inhibitors. |
|
Very
Low Viscosity Non-Toxic Secondary Refrigerant Antifreeze. Based on Potassium
Formate blended with BS6580 proven Corrosion, Scale and Biological Inhibitors. |
|